— If one wire is connected incorrectly, the reading will be 4 °C too high without triggering an alarm —

Accuracy Comparison of the Three PT100 Wiring Configurations
Is the PT100 reading consistently too high, or is the time reading inaccurate? Don't rush to replace the probe; the problem may lie in the wiring configuration.
The platinum resistance sensor PT100 itself has no polarity; however, the connecting wires do have resistance. What the instrument measures is not the resistance of the probe alone, but the total resistance of "probe + wires" —each 1 Ω of wire resistance corresponds to an approximate 2.5 °C reading deviation. A standard 10-meter copper wire has a resistance of approximately 0.2 Ω, which directly reduces the accuracy by 0.5 °C. The differences among the two-wire, three-wire, and four-wire configurations lie in how the resistance of the connecting wires is accounted for.
Three wiring standards, with errors differing by an order of magnitude
Two-wire system One wire is connected to each end of the probe; the resistance of the wires is fully included in the measured value and drifts with ambient temperature. This system is suitable only for non-critical locations where the wire length is within 5 meters and the required accuracy is ±1–3 °C, such as displaying the ambient temperature inside a cabinet.
Three-wire system One wire at one end of the probe and two wires at the other end; the instrument uses bridge compensation to cancel out the lead resistance. This requires that the three wires be made of the same material, have the same wire diameter, and be of equal length—this is the mainstream solution in industrial applications, delivering a accuracy of ±0.2–0.5 °C and remaining accurate over wiring lengths of up to 100 meters.
Four-wire configuration Two wires at each end—one for the excitation current and the other for voltage measurement—provides complete isolation from lead resistance; even with longer wires, the resulting error can be neglected, and the accuracy remains within ±0.1 °C. This configuration is the standard configuration for laboratory metrology, pharmaceutical applications, and precision temperature control in semiconductor devices.
| standard | Lead error | Typical accuracy | Applicable range | Typical scenarios |
| two-wire system | uncompensated | ±1~3℃ | ≤5 meters | Ambient temperature, cabinet temperature |
| three-wire system | Bridge compensation | ±0.2~0.5℃ | ≤100 meters | Pipes, drying ovens, process temperature control |
| four-wire system | The error is negligible | ≤±0.1℃ | Several hundred meters | Metrological calibration, semiconductors, pharmaceuticals |
Three Typical Field Scenarios Where a Single Wire Is Connected Incorrectly
1. Connect the compensation lead to the signal terminal: In a three-wire system, the individual lead is the "compensation lead," not the "reserve lead"; if it is connected to the wrong position, the compensation circuit will fail immediately, and the instrument will calculate the reading as if it were a two-wire system—when the conductor resistance is 10 Ω, the reading will be elevated by more than 4 °C, while the value "appears normal" and no alarm will be triggered.
2. The three wires have inconsistent specifications: after replacing a section of cable and passing the wires through a terminal block at an intermediate point, the resistances of the three wires are no longer equal; compensation is reduced to only half its original value, and the readings drift with seasonal temperature changes. Despite extensive troubleshooting, no fault in the probe can be identified.
3. Instrument terminals are not shorted as shown in the diagram: since the instrument does not support a three-wire configuration and the common terminal has not been shorted, the error is directly doubled.
30-Second Self-Assessment Method After disconnecting the power, use a multimeter to measure the resistance between the two leads on the same side of the probe—in a three-wire system, this resistance should be close to 0 Ω (difference <0.05 Ω); then connect a resistor box to simulate 100 Ω, and the instrument should display 0 °C. If both tests fail, first check the wiring and then replace the probe.
The guiding principle for selecting a wiring scheme can be summed up in one sentence: first determine the required accuracy, then determine the wiring scheme; the greater the distance, the more compensation is required.