Leave Your Message

Temperature Transfer and Conversion Module

Temperature transfer conversion module is for Thermistor or thermocouple temperature sensor with matching current or Dedicated module for voltage output; The module adopts imported original Device installation, SMT process assembly, stable and reliable performance,Small size, easy to install.

    Features

    1. Imported core, according to the application of a variety of principles of the chip to choose.
    2. Optional output: 4-20mA, RS485, etc.
    3. Good long-term stability, excellent anti-interference performance, etc.
    4. Obtain ROHS and CE certification.

    Application

    Intelligent temperature transmission isolation safety gate (thermocouple, thermal resistance input) for thermocouple, thermal resistance or other millivolt signals in dangerous areas of the field.
    The input, after isolation, is converted into a standard DC signal output to the safe zone of the control.
    System or other instrument. It's an intelligent temperature transfer isolation safety grid, yes.
    USB interface, the input thermocouple can be programmed by PC and control software.
    Type and range range, and the zero and full degree of the output signal can be checked.
    Single channel, one input, one output. The isolation safety fence is self-contained.
    The input/output/power channels are isolated from each other by the DC power supply.

    Technique Parameter

    ● Power supply
    Power supply voltage range: 20~30VDC
    Rated power supply voltage: 24VDC
    Current consumption (24VDC power supply) : <30mA
    ● Input from the danger zone
    (Can be set by PC and software programming)
    Thermal resistance: Pt100, Cu50, etc
    Temperature range: depending on the type of sensor connected (see range table)
    Optional millivolt signal input: ±80mV
    Minimum millivolt range: 5mV
    ● Output to safety zone
    Output current: 4~20mA; Other specified current
    Output voltage: 1~5V; Other specified voltages
    Load resistance: 4~20mA output, ≤350Ω(factory default, can specify the load)
    ● Comprehensive general parameters
    Cold end compensation accuracy: ±1℃ (compensation range -20℃~+60℃)
    (Cold end resistance has been installed inside the isolation safety grid)
    Temperature drift: 0.01%F.S./℃
    Response time: < 0.4s
    Isolation capacity: between input - output - power supply 2.5KV, 1min, 50Hz
    Insulation resistance: Input, output and power ≥100MΩ / 500VDC
    Case material/Protection grade: Flame retardant ABS/IP20
    Dimensions: 16×116×110(mm)
    Working temperature: -20℃~ +60℃
    Applicable to connected field equipment and hazardous areas: thermocouple temperature
    The sensor. Zone 0, Zone 1, Zone 2; IIA, IIB, IIC danger zones
    ● Safety explosion-proof certification parameters
    Explosion-proof grade mark: [Exia Ga]IIC
    Security certification parameters: Um = 250VAC/DC Uo = 10.5VDC Io =5mA
    Po = 13.2W Lo = 100mH Co =1.7μF

    Terminal Connection Diagram